Available as Active High and Active Low
Basic Operation
Solar Converters Inc. Voltage Controlled Switch is a simple power relay switch which has user adjustable voltage setpoints. Normally the relay is not powered, connecting the common terminal (C) to the normally closed (NC) terminal.
The Active High unit monitors the incoming voltage and if it goes over the "high" setpoint for 3 seconds, the power relay will switch on, connecting the common terminal (C) to the normally open (NO) terminal.
Once the relay is on, the unit monitors the incoming voltage and if it goes below the "low" voltage setpoint for 3 seconds, the unit will turn off the power relay, connecting the common (C) terminal to the normally closed (NC).
Active Low operation is identical to the Active High listed above BUT the relay operation is opposite.
In Active Low operation, the unit monitors the incoming voltage and if it goes below the "low" setpoint for 3 seconds, the power relay will switch on, connecting the common terminal (C) to the normally open (NO) terminal.
Once the relay is on, the unit monitors the incoming voltage and if it goes above the high voltage setpoint for 3 seconds, the unit will turn off the power relay, connecting the common (C) terminal to the normally closed (NC).
· Single unit 12, 18, 24, 36 and 48 V operation
· Easy to setup, setpoints have a 1/10 th. scale factor. To set 12 V, set the setpoint to 1.2V
Electrical Specifications
Nominal Voltage (V)
|
12
|
18
|
24
|
36
|
48
|
Max Output (A)
Basically rating of 30 amp relay
|
30
|
30
|
30
|
15
|
03
|
Maximum Voltage (V)
|
63
|
|
|
|
|
Minimum Voltage (V)
|
10
|
|
|
|
|
Self Consumption
|
|
|
|
|
|
Quiescent (ma)
|
17
|
17
|
17
|
17
|
17
|
Relay on (ma)
|
75
|
57
|
47
|
37
|
32
|
Standard Delay on action is 3 seconds low, 1 second high
Delay of 0.1 sec to 45 Seconds are available. Please specify at time of ordering
Default relay position on startup between voltage setpoint - Relay Off
Mechanical Specifications
· Weight:
o 0.3 lbs. approx., 1 lbs. approx with enclosure
· Size:
o 4.125" x 2.8" x 2" open frame as shown above
· Available in enclosure with 1/2" conduit knockouts
· Connections:
o Power:
o Eurostyle Terminal Strip #6 AWG
· Operating Temperature:
o -40 to 60 deg. C
· Humidity:
o 0 - 90 % non-condensing
Applications
· Load Controller
· Low Voltage Disconnect
· Grid Intertie Controller
· Wind/hydro Dump Controller
· Generator Start Controller
· Simple Charge Controller
· Battery Vent Controller
· Load Controller
· Low Voltage Disconnect
· Generator Start Controller
Features
· Wide Voltage range
· Fused and Transient protected
· Adjustable high and low setpoints